한국어 English Chinese Russian

CIE-H12A / 1-Port Remote I/O Controller

CIE-H12A is a remote I/O controller that supports 2 digital input ports (Dry & Wet Contact) and 1 output port (Relay Switch). CIE-H12A meets industrial temperature specifications and provides the ability to monitor and control digital input ports and digital output ports over a network. Also, the existing contacts can be controlled through the network, enabling efficient management of I/O equipment from remote locations. CIE-H12A features two input ports and one output port, making it a cost-effective product for sites with one or two targets for control and monitoring.

When controlling the contacts of CIE-H12A, Modbus/TCP protocol is used, and since the Web method is also supported, you can control the output port through the Web page from anywhere. Also, the Web page can be changed to suit the user’s purposes. Besides, a Macro function that automatically controls the output port is provided by a simple logic formula according to the input port.

CIE-H12A can be used in any environment where I/O devices need to be controlled and monitored, especially for applications such as Remote PC Power Control, Internet Switch, etc.

Product Specification Videos Download Ordering Info
CIE-H12A main features

  • Affordable for small sites
  • 2 x input port (dry/wet contact)
  • Monitor & control via Modbus/TCP or Web
  • Controlled by simple logic formula operating autonomously
  • Web-based control over custom web page
  • Can be used as Internet switch
  • Free Modbus/TCP program (ModMap)


* The above information is subject to change and Sollae Systems is not responsible for any changes.
Digital Input Port
Number of Ports2
InterfaceIsolated by Photo-coupler
Electric ParameterMAX VIL=1.2V, MIN VIH=2.2V
Maximum Input VoltageDC 24V


Digital Output Port
Number of Ports1
InterfaceIsolated by Relay
Relay Capacity5A(DC28V)


Network Physical Interface
Network Interface10Base-T/100Base-TX Ethernet(RJ45)
Ethernet Speed Auto Sense
1:1 or Cross-over Cable Auto Sense
1000 VAC Isolation


Software Functions
ProtocolsTCP, UDP, IP, ICMP, ARP, DHCP, PPPoE, TELNET
TFTP, DNS, DDNS, HTTP, Modbus/TCP, SMTP
SecurityIP & MAC filtering - Restrict host or network
Password for Configuring
Digital I/O Port
Communication Mode
Modbus/TCP, HTTP, Stand alone(by simple equation)
Additional FunctionsRemote Debug Function


Indicators(LEDs)
StatusYellow, The Current Status
Ethernet Link/RXD/TXDGreen
Digital InputYellow x 2
Digital OutputGreen


Management
ezManagerConfiguration and Monitoring Tool through Ethernet
TelnetTelnet Login


Supplementary Software
ezManagerConfiguration Tool for Windows
ModMapManagement Tool of I/O controllers for Windows


Dimension
Size96mm x 57mm x 24mm


Operating Software
Input VoltageDC 5±0.5V
Current Consumption300mA typical
Operating Temperature-40℃ ~ +85℃
Storage Temperature-40℃ ~ +85℃


Certificate
KCRegistration(KN 32, KN 35)
CEEMC 2014/30/EU, RoHS 2011/65/EU







Part Number Description Note
CIE-H12A-BO cie-h12a
CIE-H12A
 
Optional Accessories Description Note
BRACKET_BLACK bracket
Datasheet
MOUNTER mounter
Datasheet
DVD dvd
DVD with configuration tools and documentation