한국어 English Chinese Russian
bannerbar

Q&A



Your information is protected by SSL.
No. 1494 Re: Desactivate Outputs if no connection 2017-05-15

In previous reply, I show how to configure the feature you want.

It'ss worth to note that, if that option is enable, output port is set to initial state when TCP connection is closed.

If you manually close the TCP connection in the software, output port will be initialized immediately.

In case the cable connection is lost, it takes about one minute to detect TCP connection is closed. Therefore, it takes about one minute before initializing.

Thank you,

Best regard,

> Fábio Oliveira wrote:
> ------------------------------------
> Good afternoon,
>
> I would like to know if it is possible to configure the CIE-H10 to do the following:
>
> 1. A normal connection is made in Modbus/TCP with the module.
> 2. Some outputs are activated;
> 3. Suddenly, the cable information is disconnected or some other line issue breaks the connection between the PC program and the module.
> 4. All the outputs should be deactivated.
>
> I cannot make the module to put all outputs off when there is no connection. I can put all outputs off when I normally disconnect from the module ( I checked the box "Initialize the output port state" in the ez TCP manager).
>
> So, is there a way to make all the outputs off if the connection is abnormally lost?
>
> Thank you very much.

Writer Sollae Systems Company