No. 530 Re: macro to CIE-H10 2009-11-12

Hello,

When using the Macro mode, you can't control the output ports of CIE-H10 with Modbus/TCP.
In that situation, the ouput ports can be controlled by only the macro function.
This option can be called stand alone operation.
To use this, you should know about the operaters "*", "+" and "/".
Each input ports can be a term of the simple formula based on boolean algebra.
Please refer to the manual to find how to use them.

In the conclusion, when you use the macro mode, it doesn't allowed to controlling output ports via Modbus/TCP or HTTP.

Have a nice day!

> sam wrote:
> ~~~~~~~~~~~~~~~~~~~~~~~~~~~
> Hy,
> I would like to know, how to use the macro mode?
> I try to run with macro's case option in "ezTCP manager.exe". But when i check this case, i can't send a modbus message whith another software.
>
> Thanks for your answer.
> Sam

Writer Sollae Systems Company