No. 1743 Re: Re: RS422 converter 2020-07-20

Good morning,

Please see the attachment file for information.

gr. Johan


> Sollae Systems wrote:
> ------------------------------------
> Dear Johan,
>
> Thank you for your interest in our products.
>
> It is possible to use our products to make the connection between a Mitsubishi PLC and a Monitouch HM over Ethernet.
>
> You may need to choose the product depends on how Mitsubishi PLC and a Monitouch HM interact with each other.
> In case of using Modbus RTU or ASCII, Modbus Gateway can be used.
> In other cases, RS422 to Ethernet converters can be used.
>
> To choose the right products, please check which protocol Mitsubishi PLC and a Monitouch HM interact with each other.
> If you can send us the model name of the devices in your system and the protocol you are using, we could provide a more detailed suggestion.
>
> We hope the above is useful to you.
> Please feel free to contact us if you need any further information.
>
>
> > Johan wrote:
> > ------------------------------------
> > Hello.
> >
> > Normally we have a RS422 4-wire connection between a Mitsubishi PLC and a Monitouch HMI.
> >
> >
> > case:
> > Is there a possibility to connect more HMI's with RS422(4wire), on one PLC with RS422 connection, using RS422 to Ethernet converters.
> >

Attachment 20200720_RS422 - Ethernet 200720.zip
Writer Johan Company Teunis Industrie